RMC No. 64-2014 publishes public building standards for Yolanda rehabilitation, affecting contractors, designers, suppliers, and government project compliance.
Government agencies, contractors, designers, suppliers, and businesses involved in Typhoon Yolanda rehabilitation projects must align public building plans with the minimum architectural, structural, electrical, mechanical, fire protection, and accessibility standards published under RMC No. 64-2014. While this issuance does not impose a new tax rate or filing deadline, it matters immediately for companies participating in public construction, procurement, rehabilitation, reconstruction, design, engineering, and supply contracts because non-conforming designs may be rejected, delayed, or exposed to compliance issues under building, fire, sanitation, accessibility, plumbing, electrical, and structural standards.
What RMC No. 64-2014 Changed
RMC No. 64-2014 published, for the guidance of all concerned, the full text of the memorandum from the Office of the Presidential Assistant for Rehabilitation and Recovery Infrastructure Cluster dated June 11, 2014, entitled “Minimum Performance Standards and Specifications for Public Buildings.” The standards apply to the preparation of design plans for the rehabilitation and reconstruction of office buildings and other vertical structures damaged by Typhoon Yolanda.
The practical effect is that public building rehabilitation projects must not be treated as ordinary repair works based only on available budgets or existing layouts. The standards provide specific space requirements, site planning rules, structural design assumptions, wind and seismic design parameters, utility requirements, and minimum performance specifications for public offices, municipal buildings, multi-purpose buildings, public gymnasiums, and public markets.
For accountants, CFOs, and business owners, the key search issues are not limited to “RMC No. 64-2014.” The practical topics include “Yolanda rehabilitation public building standards,” “minimum performance standards public buildings Philippines,” “public market design requirements Philippines,” “DPWH public building specifications,” and “government construction compliance requirements.” These matter when preparing bids, validating project cost estimates, reviewing design variations, and documenting compliance for government contracts.
Who Is Affected
The most directly affected parties are government agencies, local government units, public officers, architects, engineers, project managers, contractors, subcontractors, construction suppliers, and consultants involved in public buildings damaged by Typhoon Yolanda. Businesses bidding for government rehabilitation or reconstruction projects must pay close attention because the standards affect project design, costing, materials, fire protection, water supply, drainage, electrical works, mechanical systems, and site planning.
Although the issuance is a Revenue Memorandum Circular, it is not a tax assessment circular, withholding tax circular, VAT circular, or income tax circular. It does not create a new BIR tax filing obligation. Instead, it uses the BIR circular mechanism to give wide publicity to standards relevant to government rehabilitation and reconstruction. For private businesses, the compliance relevance arises where they contract with government, supply materials, provide professional services, or participate in public infrastructure work connected with Yolanda rehabilitation.
Key Architectural and Space Requirements
For public office buildings, RMC No. 64-2014 sets recommended space requirements. A main lobby should provide 0.25 square meter per person, with a minimum waiting or standing room standard of 0.28 square meter per person. Rank-and-file working areas are recommended at 4.00 to 6.00 square meters per person. Conference rooms are recommended at 1.20 square meters per person, including aisles and demonstration space.
Toilet facilities must follow the Revised National Plumbing Code of the Philippines. Employee toilet facilities require one water closet for 1 to 15 users, two water closets for 16 to 35 users, and three water closets for 36 to 55 users, for male and female users. Lavatories are required at one lavatory per 40 male and female users, or one lavatory for every two water closets. Public toilet facilities require one water closet for every 1 to 100 female users, one water closet for every 1 to 200 male users, one urinal for every 1 to 100 male users, and one lavatory for every two water closets. PWD facilities require one water closet or toilet stall with clear dimensions of 1.70 meters by 1.80 meters per male and female, or one common PWD toilet for male PWDs, female PWDs, and the elderly.
Hallways, corridors, and stairways must have a minimum clear width of 1.20 meters, with 2.40 meters identified as ideal, or 0.60 meter width per person. At least two fire escape stairs or exits are required where the number of occupants exceeds 30 for offices or exceeds 50 for assembly areas such as training rooms, halls, gymnasia, and auditoriums, subject to compliance with the New Fire Code of the Philippines and the National Building Code, with the more stringent provision controlling.
Municipal Buildings, Multi-Purpose Buildings, and Public Markets
RMC No. 64-2014 provides indicative space standards for offices in a typical municipal building. The Mayor’s Office is recommended at 48.00 to 50.00 square meters, while the Vice Mayor’s Office is recommended at 40.00 to 48.00 square meters. A chief’s office for several municipal departments is generally indicated at 12.00 square meters, with staff areas at 4.00 to 6.00 square meters per person and storage areas commonly ranging from 6.00 to 10.00 square meters depending on the office.
For a multi-purpose building or public gymnasium, the issuance identifies a total recommended area of 1,052.7 square meters. This includes a 28.00 meter by 14.00 meter basketball court with an area of 392.00 square meters, a stage of 4.00 meters by 11.2 meters or 44.80 square meters, circulation and bleachers of 506.9 square meters, a PWD toilet of 2.00 meters by 2.00 meters or 4.00 square meters, and separate locker, shower, and toilet spaces for male and female users. For bleachers, seat width must not be less than 450 millimeters nor more than 480 millimeters under the referenced building code rule.
For public markets, site selection must consider physical site condition, infrastructure and utilities, accessibility, and location relative to the population or service center. Market sites should be in designated commercial zones or areas, preferably accessible through an arterial street, with service access for trucks. The site must be at least 50 meters away from schools, religious institutions, public offices, funeral establishments, and other public gathering places, and 25 meters away from abattoirs and sources of contamination. The market should be accessible by walking distance of 0.75 kilometer or an average 15-minute travel time by public vehicles.
Public Market Design, Parking, Stalls, and Utilities
The standards allocate public market lot use at 50% to 70% building area and 30% to 50% open space. For market building area distribution, the recommended allocation is 55% to 60% selling area, 35% to 40% circulation, and 5% to 10% facilities, toilets, utility rooms, and offices. A minimum 5.00-meter landscaping and buffering area may be provided along the site perimeter.
The market height level is set at 4.50 meters, measured from the floor level to the top of the roof beam or bottom of the truss. PWD accessibility features under B.P. Blg. 344 must be integrated. Potable water must be adequate, with the fish and eatery sections having one 12 millimeter faucet in each stall, while meat and vegetable sections must have at least one 12 millimeter faucet for every five stalls.
Drainage and sewage standards are specific. At least one floor drain must be provided for every 46.50 square meters of floor area. The floor slope must not be less than 20.50 millimeters per meter to the drainage outlet. Fish and meat sections should have catch basins for retaining solids. Sewer lines from toilets and urinals must not be connected with market drainage lines, and all floor drains must have a deep seal trap such as a P-trap or U-trap.
Parking must also be planned. For every 100 square meters of leasable stall floor area, four parking spaces are assumed, each measuring 2.50 meters by 5.00 meters. The hawker’s plaza should not exceed 60% of the market core, except for markets operating only once or twice per week. The bagsakan or wholesale area is computed at around 10% to 13% of the total built-up area. Market stall areas are expected at approximately 60% of total floor area, circulation at 35%, and offices, toilets, and utility rooms at 5%.
Structural, Wind, Seismic, and Material Standards
Public buildings and structures must be designed under the latest edition of the National Structural Code of the Philippines, Volume 1, 2010, and P.D. No. 1096, the National Building Code of the Philippines, including its revised implementing rules. The structures are required to be designed to last at least 50 years.
The standards classify public school buildings, fire and police stations, aviation control towers, hospitals, and evacuation centers as essential facilities. Municipal buildings, covered courts, multi-purpose buildings, housing, and public markets fall under standard occupancy. For wind load, the basic wind speed is 250 kph for Zone I, 250 kph for Zone II, and 150 kph for Zone III. The wind importance factor is 1.15 for essential facilities and 1.00 for standard occupancy.
For seismic load, Palawan, Sulu, and Tawi-Tawi are identified under Zone 2, while the rest of the Philippines are under Zone 4. Public buildings and structures must be designed to withstand earthquakes with a seismic zone factor of 0.20 for Zone 2 and 0.40 for Zone 4. The seismic importance factor is 1.50 for essential facilities and 1.00 for standard occupancy. In the absence of a geotechnical report, the default soil profile type SE is used for earthquake load computation.
Minimum live loads include 2.4 kPa for offices, 1.9 kPa for school classrooms, 2.4 kPa for restrooms, 3.8 kPa for corridors above the ground floor, 4.8 kPa for lobbies and ground floor corridors, 4.8 kPa for exit facilities, 6.0 kPa for wholesale stores, and 2.9 kPa for assembly areas and auditoriums with movable seats. For roof truss design, a roof live load of 0.60 kPa is used due to the large tributary area of the roof.
Concrete must develop minimum 28-day compressive strength of 20.7 MPa for foundations, elevator shafts, columns, slabs, and beams, and 17.2 MPa for slab on grade. Structural steel must have a minimum yield strength of 248 MPa or 36,000 psi conforming to ASTM A36. Non-load bearing concrete blocks must have minimum compressive strength of 2.40 MPa, while load bearing concrete blocks must develop 6.90 MPa.
Electrical, Mechanical, Water, and Fire Protection Requirements
Electrical design must follow the Philippine Electrical Code. Service entrance conduits must use rigid steel or intermediate metallic conduit for conductors with insulation, while underground conduit runs must be encased in concrete envelope or reinforced steel when crossing roadways. Electric service metering equipment must be installed at a minimum height of 1,600 millimeters from the natural grade line to the center of the equipment.
Lighting standards are also specified. Municipal building tasks such as detailed drafting and designing require 2,200 lux, while rough layout drafting requires 1,600 lux. Accounting office tasks such as auditing, tabulating, bookkeeping, business machine operation, and computer operation require 1,600 lux. Corridors require 220 lux. For multi-purpose buildings, gymnasium exhibitions or matches require 540 lux, general exercising requires 320 lux, assemblies require 110 lux, and dances require 50 lux. For public markets, circulation areas require 320 lux, merchandising service areas require 1,100 lux, and stockrooms require 320 lux.
Air-conditioned rooms or enclosed spaces must maintain comfortable cooling at 20 to 24 degrees Celsius and 50% to 55% relative humidity, with air movement from 4.57 to 7.6 meters per minute within the living zone. Gravity-ventilated toilets require exhaust ducts and inlet exhaust grilles, with 50 cubic feet per minute per fixture bowl or urinal bowl, or 4 to 6 air changes per hour for excessive toilet areas.
Fire sprinkler pipes and tubes must be designed to withstand a working pressure of not less than 1,206 kilopascals. Hydrostatic testing must be made at not less than 1,378 kilopascals for two hours. Flushing requirements are also stated: not less than 2,836 liters for 152 millimeter diameter pipe, 3,785 liters for 203 millimeter diameter pipe, 5,678 liters for 254 millimeter diameter pipe, and 7,570 liters for 305 millimeter diameter pipe.
Deadlines, Effective Date, and Penalties for Non-Compliance
RMC No. 64-2014 is dated July 10, 2014, while the infrastructure memorandum it publishes is dated June 11, 2014. The circular does not state a separate tax filing deadline, transition period, BIR penalty, surcharge, interest rate, or compromise penalty. It also does not impose a new VAT, withholding tax, income tax, documentary stamp tax, or percentage tax requirement.
However, businesses should not treat the absence of a tax penalty as permission to ignore the standards. The document repeatedly anchors compliance on other applicable laws and codes, including the National Building Code of the Philippines, the New Fire Code of the Philippines, the Revised National Plumbing Code, the Sanitation Code of the Philippines, the Water Code, the Accessibility Law, the Philippine Electrical Code, and the National Structural Code of the Philippines. Non-compliance may therefore affect permitting, acceptance of works, contractual payments, project approval, procurement compliance, and exposure under the applicable regulatory framework governing construction and public infrastructure.
Practical Steps for Businesses and Government Contractors
Businesses involved in Yolanda rehabilitation and public building projects should first map their role in the project: designer, contractor, supplier, project manager, government consultant, or subcontractor. Each role must determine which standards apply to its deliverables. A contractor constructing a public market, for example, must pay attention to site access, stall sizing, drainage, waste management, water supply, fire protection, parking, and circulation. An engineering consultant must focus on wind load, seismic load, live load, soil investigation, foundation design, concrete strength, reinforcing steel, structural steel, and sprinkler pressure requirements.
Second, project costing should be revisited against the minimum standards. Some figures directly affect cost, such as the 50-year design life, 250 kph wind speed in Zones I and II, 1.50 seismic importance factor for essential facilities, 4.50 meter market height level, standby generator requirement for public markets, one portable fire extinguisher recommended for every market stall except wet and semi-wet stalls, and specific drainage and water supply specifications.
Third, bid documents, technical proposals, design drawings, bills of quantities, and variation orders should expressly align with the standards. This is particularly important where a business seeks payment from government funds, defends a variation order, or explains why certain materials or systems are necessary. The more specific the compliance reference, the easier it is to support contract price, scope, and acceptance.
Fourth, companies should retain documentation showing compliance. This includes design computations, architectural plans, plumbing layouts, electrical schedules, fire protection calculations, material specifications, geotechnical reports where required or recommended, and inspection records. These records may become important in procurement review, audit, contract disputes, or claims involving project defects or delays.
How Ablola, Saribong & Gueco Can Help
RMC No. 64-2014 is not a conventional tax circular, but it is highly relevant to businesses dealing with government infrastructure, rehabilitation projects, public procurement, construction contracts, and compliance-sensitive public works. For contractors, suppliers, architects, engineers, and LGU project partners, the key legal risk is not only tax compliance but also whether the project documents, contracts, pricing, warranties, and deliverables properly reflect the mandatory public building standards and related Philippine regulatory requirements.
Ablola, Saribong & Gueco assists businesses with BIR issuances, government contract compliance, procurement documentation, construction-related legal review, regulatory risk assessment, and dispute prevention. If your company is bidding for, implementing, auditing, or disputing a public infrastructure or rehabilitation project, consult ASG Law before signing, billing, or accepting non-standard contract terms. Visit MakatiLawFirm.com to speak with a Philippine tax and business law team that understands both regulatory compliance and commercial realities.